eneral specifications
|
Signal type
|
Analog output
|
Functional safety related parameters
|
Safety Integrity Level (SIL)
|
SIL 2
|
Supply
|
Connection
|
Power Rail or terminals 11+, 12-
|
Rated voltage
|
20 ... 35 V DC
|
Ripple
|
within the supply tolerance
|
Power dissipation
|
1.1 W at 20 mA into 10 V (equivalent to 500 Ω) load
|
Power consumption
|
1.3 W
|
Input
|
Connection side
|
control side
|
Connection
|
terminals 7-, 8+
|
Voltage drop
|
approx. 4 V or internal resistance 200 Ω at 20 mA
|
Input resistance
|
> 100 kΩ, when wiring resistance in the field < 50 Ω or > 800 Ω at 20 mA
|
Current
|
4 ... 20 mA limited to approx. 25 mA
|
Output
|
Connection side
|
field side
|
Connection
|
terminals 1+, 2-
|
Current
|
4 ... 20 mA
|
Load
|
100 ... 700 Ω
|
Voltage
|
≥ 14 V at 20 mA
|
Transfer characteristics
|
Accuracy
|
0.1 %
|
Rise time
|
< 100 ?s at bounce from 10 ... 90 %
|
Indicators/settings
|
Display elements
|
LEDs
|
Labeling
|
space for labeling at the front
|
Directive conformity
|
Electromagnetic compatibility
|
|
|
Directive 2014/30/EU
|
EN 61326-1:2013 (industrial locations)
|
Conformity
|
Insulation coordination
|
EN?50178:1997
|
Galvanic isolation
|
EN?50178:1997
|
Electromagnetic compatibility
|
NE 21:2006
|
Degree of protection
|
IEC 60529:2001
|
Ambient conditions
|
Ambient temperature
|
-20 ... 60 °C (-4 ... 140 °F)
|
Mechanical specifications
|
Degree of protection
|
IP20
|
Connection
|
screw terminals
|
Mass
|
approx. 100 g
|
Dimensions
|
20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch) , housing type B1
|
Mounting
|
on 35 mm DIN mounting rail acc. to EN 60715:2001
|
Data for application in connection with hazardous areas
|
EU-Type Examination Certificate
|
BAS 00 ATEX 7215
|
|
Marking
|
?II (1)G [Ex ia Ga] IIC ,? ?II (1)D [Ex ia Da] IIIC ,? ?I (M1) [Ex ia Ma] I
|
Certificate
|
T?V 99 ATEX 1499 X
|
|
Marking
|
?II 3G Ex nA II T4 [device in zone 2]
|
Directive conformity
|
|
|
Directive 2014/34/EU
|
EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
|
International approvals
|
FM approval
|
|
|
Control drawing
|
116-0129
|
UL approval
|
|
|
Control drawing
|
116-0173 (cULus)
|
IECEx approval
|
IECEx BAS 16.0045
|
|
Approved for
|
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
|